Input signals, Output signals, Input signals output signals – Emerson Transmitters and Discrete Controllers Series 3000 User Manual

Page 6

background image

6

Micro Motion

®

Series 3000 Transmitters and Discrete Controllers

Input signals

Output signals

Non-intrinsically safe input signals

One 2-wire
frequency/pulse input

Frequency range

0–20,000 Hz

Minimum pulse width

25

μ-sec

Power

Sourcing or sinking

Voltage

0–0.8 VDC low state

3–30 VDC high state

Current

Nominal 5 mA pull-up

Two discrete
momentary inputs

Pulse width

0.15 sec minimum

Voltage

0–0.8 VDC low state

3–30 VDC high state

Dry contacts

Intrinsically safe input signals

One 4-wire Coriolis sensor signal input with ground

Non-intrinsically safe output signals

Two active
4–20 mA outputs

Isolated to ±50 VDC from all other outputs and earth ground

Maximum load limit of 1000 Ohms

Output is linear with process from 3.8 to 20.5 mA per NAMUR NE43 (June 1994)

Three discrete outputs

Configurable for the application

Polarity

Active high or active low, software selectable

Power

Internal pull-up to 24 V

Voltage

24 VDC nominal

Current

Sourcing at 5.6 mA when V

out

= 3 VDC

Sinking up to 500 mA at 30 VDC maximum

One 2-wire
frequency/pulse output

Scalable to 10,000 Hz

Output is linear with flow rate to 12,500 Hz

Pulse width

50% duty cycle above the crossover frequency

(1)

(1) The crossover frequency depends on the configured value of the pulse width. At the minimum pulse width value of 0.543 ms, the

crossover frequency is 922 Hz. At the maximum pulse width value of 277 ms, the crossover frequency is 1.8 Hz.

Configurable between 0.543 ms and 277 ms

Polarity

Active high or active low, software selectable

Power

Active or passive, software selectable

Voltage

24 VDC nominal, active

30 VDC applied maximum, passive

Current

Sourcing at 10 mA at 3 VDC, active

Sinking at 500 mA, active or passive