Input signals, Output signals, Input signals output signals – Emerson Transmitters and Discrete Controllers Series 3000 User Manual
Page 6
6
Micro Motion
®
Series 3000 Transmitters and Discrete Controllers
Input signals
Output signals
Non-intrinsically safe input signals
One 2-wire
frequency/pulse input
Frequency range
0–20,000 Hz
Minimum pulse width
25
μ-sec
Power
Sourcing or sinking
Voltage
0–0.8 VDC low state
3–30 VDC high state
Current
Nominal 5 mA pull-up
Two discrete
momentary inputs
Pulse width
0.15 sec minimum
Voltage
0–0.8 VDC low state
3–30 VDC high state
Dry contacts
Intrinsically safe input signals
One 4-wire Coriolis sensor signal input with ground
Non-intrinsically safe output signals
Two active
4–20 mA outputs
Isolated to ±50 VDC from all other outputs and earth ground
Maximum load limit of 1000 Ohms
Output is linear with process from 3.8 to 20.5 mA per NAMUR NE43 (June 1994)
Three discrete outputs
Configurable for the application
Polarity
Active high or active low, software selectable
Power
Internal pull-up to 24 V
Voltage
24 VDC nominal
Current
Sourcing at 5.6 mA when V
out
= 3 VDC
Sinking up to 500 mA at 30 VDC maximum
One 2-wire
frequency/pulse output
Scalable to 10,000 Hz
Output is linear with flow rate to 12,500 Hz
Pulse width
50% duty cycle above the crossover frequency
(1)
(1) The crossover frequency depends on the configured value of the pulse width. At the minimum pulse width value of 0.543 ms, the
crossover frequency is 922 Hz. At the maximum pulse width value of 277 ms, the crossover frequency is 1.8 Hz.
Configurable between 0.543 ms and 277 ms
Polarity
Active high or active low, software selectable
Power
Active or passive, software selectable
Voltage
24 VDC nominal, active
30 VDC applied maximum, passive
Current
Sourcing at 10 mA at 3 VDC, active
Sinking at 500 mA, active or passive