Jordan Valve Mark 17X Series Flameproof Smart Positioner User Manual
Page 8

-8-
t
erMInal
o
vervIew
and
C
onneCtIons
Positioner Terminal:
IN + : Input Signal (positive)
IN - : Input Signal (negative)
OUT + : Feedback Signal (positive)
OUT - : Feedback Signal (negative)
Top Right 3 Terminals : Limit Switch 0%
Bottom Right 3 Terminals : Limit Switch 100%
Input Signal Terminal:
1.
Open terminal cover by removing set screw using a 3mm hex key
2.
There are two conduit entries on the bottom side of the positioner to allow for cable entry best suited to the
application.
3.
Locate the correct terminal for the input signal on the bottom of the positioner. Insert the terminal wiring
through the conduit entry and properly secure them to the IN+ (positive) and IN– (negative) terminals on the
plate. Tighten fasteners to 1.5Nm (13 in lbs).
4.
Close the terminal cover, and tighten the set screw stopper.
M
ark
17X S
erieS
F
laMeprooF
S
Mart
p