beautypg.com

Table 2: outlet pressure ranges, Table 3: wide-open flow coefficients – Jordan Valve Mark 630 Series - Gas Service/High Pressure Regulator User Manual

Page 3

background image

-3-

Disconnect vent line if installed.

2.

Unscrew two cap screws (9) and four cap screws

3.

(10) with hex nuts (25).
Remove the spring housing (3).

4.

Remove from the lever assembly, as a unit, the dia-

5.

phragm (11), connector head assembly (12), lower
spring guide (7) and cap screw (6).
Unscrew the cap screw (6) from the connector

6.

head (12) and disassemble the diaphragm (11).
Install a new diaphragm, making sure that it is

7.

properly centered. Reassemble connector head
assembly and lower spring guide, securely tight-
ened with the cap screw.
Engage connector head in lever assembly.

8.

Reinstall the spring housing with cap screws and

9.

nuts finger-tight only. Assure proper diaphragm
slack by slightly compressing the spring with the
adjusting screw (tighten by turning clockwise). Fi-
nally, complete the tightening of all cap screws and
nuts.

Table 1: Maximum Pressure and Pressure Drops

Port Diameter

1/8”

1/4”

3/8”

1/2”

Max. Allowable Inlet
Pressure, psig

1

1500

1500

1000

750

Max. Allowable Pressure
Drop, psid

1500

1000

500

250

† The sum of the outlet pressure setting and the maximum allowable pressure
drop determines the maximum allowable inlet pressure for a given installation.
For example, with a 3/8” seat ring orifice (maximum pressure drop of 500 psi)
and a 275 psig outlet pressure setting, the maximum inlet pressure is 775 psig
(500 psi + 275 psi + 775 psi).

Table 2: Outlet Pressure Ranges

Outlet Pressure

Range psig

27-50

46-95

90-150

150-200

200-275

275-500

Max Outlet

Pressure over

Pressure

Setting †, psig

200

200 ‡

Max Emergency

Outlet (Casing)

Pressure, psig

550

† Internal parts of the regulator may be damaged if the outlet pressure
exceeds the pressure setting beyond the amounts shown.

‡ This applies to outlet pressure settings below 350 psig only. For pressure
settings above 350 psig, outlet pressure is limited to 550 psig, the maximum
emergency outlet (casing) pressure.

Table 3: Wide-Open Flow Coefficients

Orifice Size

C

g

C

v

C

1

1/8”

13.9

0.49

28.4

3/16”

31.3

1.11

28.2

1/4”

55.1

2.03

27.2

3/8”

122.5

4.61

26.6

1/2”

216.0

8.18

26.4

Table 4: High Pressure Regulator Flow Capacities (scfh of

0.6 Specific Gravity Gas; based on 20% Droop)

Outlet

Pressure

Range

psig

Inlet

Pressure

psig

Outlet

Pressure

psig

Seat Ring Orifice Diameter (inches)

1/8

3/16

1/4

3/8

1/2

27-50

60

50

900

2000

3100

5200

8100

75

1300

28500

3800

7200

10000

100

1700

3500

5700

10500

13000

150

2600

5700

8700

13000

17000

200

3500

7800

11000

16000

19000

300

5300

10500

14000

20000

23000

400

6900

13000

17000

23000

550

9600

16000

20000

26000

600

9800

17000

21000

1050

17000

23000

27000

1500

19000

25000

46-95

60

50

800

1500

2400

4300

6400

75

1200

2100

3100

5500

8000

100

1500

3100

4200

7500

10000

150

2400

4500

6700

11000

14000

200

3400

6600

9400

14000

17000

300

5200

8900

11000

16000

20000

400

6800

11000

15000

20000

550

9500

13000

17000

23000

600

9800

14000

19000

1050

14000

19000

22000

1500

18000

24000

46-95

100

75

1700

3200

5000

8000

13000

125

2200

4300

6700

10000

15000

200

3500

7300

10000

16000

22000

250

4400

9400

1300

19000

24000

325

5700

11000

16000

23000

27000

400

7100

14000

19000

27000

575

9700

18000

23000

30000

600

9900

19000

25000

1075

18000

27000

32000

1500

23000

32000

90-150

125

100

2000

3600

5500

9200

13000

150

2500

4600

6800

11000

16000

200

3600

6600

9400

13000

22000

250

4400

8500

11000

18000

26000

300

5300

9800

14000

21000

30000

350

6100

10000

16000

25000

32000

400

7000

13000

18000

27000

600

9500

18000

23000

35000

1100

19500

28000

35000

1500

25000

35000