Yaskawa V1000-Series Option SI-EM3D/V Dual Port EtherNet Modbus TCP/IP Technical Manual User Manual
Page 47

Fault Condition
Fault Declared
Status Value
(U6-98/U6-99)
Description
Duplicate IP Address
BUS ERROR
1102
This node and at least one other node have the same IP
Address.
Default MAC Address
None
1103
Factory default MAC Address programmed into the
option. Return for reprogramming.
Network Link Down
BUS ERROR
1104
No network link to option.
Hardware Error
BUS ERROR
1105
Option card hardware has stopped functioning. Cycle
power to the drive.
Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99 stores
the new fault status value.