F7 monitor list, Programming 189, Monitor – Yaskawa F7 Drive Programming Manual User Manual
Page 197

Programming 189
F7 Monitor List
Table A.2 F7 Monitor List
Parameter
No.
Parameter Name
Digital Operator Display
Description
Display Units
Monitor
U1-01
Frequency Reference
Frequency Ref
Frequency reference (speed command) monitor when in
REMOTE mode, frequency reference (speed command)
setting location when in local mode or b1-01 = 0.
Set by o1-03.
U1-02
Output Frequency
Output Freq
Output frequency
Set by o1-03.
U1-03
Output Current
Output Current
Output current
0.01A
U1-04
Control Method
Control Method
Control method set in A1-02.
0 = V/F without PG
1 = V/F with PG
2 = Open Loop Vector
3 = Flux Vector
-
U1-05
Motor Speed
Motor Speed
Motor speed feedback
Set by o1-03.
U1-06
Output Voltage
Output Voltage
Output voltage
0.1Vac
U1-07
DC Bus Voltage
DC Bus Voltage
DC Bus Voltage
1Vdc
U1-08
Output Power
Output kWatts
Output power
0.1kW
U1-09
Torque Reference
Torque Reference
Torque reference
0.1%
U1-10
Input Terminal Status
Input Term Sts
Input terminal status
-
U1-11
Output Terminal Status
Output Term Sts
Output terminal status.
-
0
1: FWD. run
(Terminal S1) is ON.
1: REV. run
(Terminal S2) is ON.
1: Multi-function input 1
(Terminal S3) is ON.
1: Multi-function input 2
(Terminal S4) is ON.
1: Multi-function input 3
(Terminal S5) is ON.
1: Multi-function input 4
(Terminal S6) is ON.
1: Multi-function input 5
(Terminal S7) is ON.
1: Multi-function input 6
(Terminal S8) is ON.
0 0 0 0 0 0 0
1: Multi-function Output 1
(Terminal M1-M2) is ON.
1: Multi-function Output 2
(Terminal M3-M4) is ON.
1: Multi-function Output 3
(Terminal M5-M6) is ON.
0: Not used
1: Fault output
(Terminal MA-MB-MC) is
ON.
0 0 0 0 0 0 0 0