Programming 130 – Yaskawa F7 Drive Programming Manual User Manual
Page 138

Programming 130
Torque limit is activated in both the speed and torque control when operating in open loop vector or flux vector control methods
(A1-02 = 2 or 3). If the multi-function analog input is programmed for “10: Forward Torque Limit”, “11: Reverse Torque
Limit”, “12: Regen Torque Limit”, or “15: FWD/REV Torque Limit”, the Drive uses the lower value of either L7-0x or analog
input torque limit.
Fig. 94 Torque Limit - 4 Quadrant Operation
The following block diagram shows the relationship between torque limit using parameter settings and torque limit using multi-
function analog inputs.
Fig. 95 Torque Limit Block Diagram
REV Run Regen
L7-04
Positive Torque Reference
Negative Torque Reference
FWD Motor Rotation
REV Motor Rotation
REV Run Motor
L7-02
FWD Run Regen
L7-03
FWD Run Motor
L7-01
Quadrant 1
Quadrant 2
Quadrant 3 Quadrant 4
10: Fw d Torque Lim it
11: R ev Torque Lim it
12: R egen Torque Lim it
15: Torque Lim it
M ult-function A nalog Input
Term inal
A 2 or A 3
A
D
M in
M in
M in
M in
P ositive
torque
forw ard drive,
forw ard torque
f
r
reverse drive,
reverse torque
L7-01 Forw ard Torque Lim it
L7-02 R everse Torque Lim it
L7-03 Forw ard R egen T orque Lim it
L7-04 R everse R egen Torque Lim it
M in
M in
reverse positive regenerative torque
forw ard negative regenerative torque
M in: M inim um value priority circuit
M in
M in
M in
M in
M in
M in
175% of D rive rated current
SFS
SFS
SFS
SFS
rg
fg
C onstants
64 m s
Forw ard T orque Lim it
R everse Torque Lim it
Forw ard R egen Torque Lim it
R everse R egen Torque Lim it
Terminal
A2 or A3
Multi-function Analog Input
10:Fwd Torque Limit
11:Rev Torque Limit
12:Regen Torque Limit
15:Torque Limit
Positive
torque
M in
M in
forward drive,
forward torque
rg
fg
reverse positive regenerative torque
forward negative regenerative torque
M in:Minimum value priority circuit
reverse drive,
reverse torque
M in
M in
M in
M in
M in
M in
M in
M in
M in
M in
SFS
SFS
SFS
SFS
64 ms
Constants
L7-01 Forward Torque Limit
L7-02 Reverse Torque Limit
L7-03 Forward Regen Torque Limit
L7-04 Reverse Regen Torque Limit
175% of Drive rated current
Forward Torque Limit
Reverse Torque Limit
Forward Regen Torque Limit
Reverse Regen Torque Limit