8 Configuring CompoNet Messaging
36
YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual
◆
Drive Operation on CompoNet
■
Polled Assemblies Quick Reference
Refer to the CompoNet Option SI-M3/V Technical Manual for details on polled assemblies
and other message types.
Output Assemblies/Drive Consumes
Input Assemblies/Drive Produces
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
20
CompoNet
Basic
Speed
Control
0
-
-
-
-
-
Fault
Reset
-
Run Fwd
1
-
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
21
CompoNet
Extended
Speed
Control
0
-
Net Ref
Net Ctrl
-
-
Fault
Reset
Run
Rev
Run
Fwd
1
-
2
Speed Reference (Low Byte)
3
Speed Reference (High Byte)
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
70
CompoNet
Basic
Speed
Control
0
-
-
-
-
-
Running 1
-
Faulted
1
-
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
71
CompoNet
Extended
Speed
Control
0
At Speed
Ref from
Net
Ctrl from
Net
Ready
Running 2
(REV)
Running 1
(FWD)
Warning
Faulted
1
State
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)