7 Troubleshooting

YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual

33

Minor Faults and Alarms

Digital Operator Display

Fault Name

to

oFA30 to oFA43

Option Fault (port A)

Communication ID error

Cause

Possible Solution

Option hardware fault

Replace the option. Contact Yaskawa for assistance.

Digital Operator Display

Minor Fault Name

AEr

MAC ID Setting Error
Option MAC ID is outside the acceptable setting range.

Cause

Possible Solutions

Minor Fault

(H2-†† = 10)

MAC ID is set outside the possible
setting range.

Reset the MAC ID in F6-40 to an allowable value.

Yes

Digital Operator Display

Fault Name

CALL

Serial Communication Transmission Error

Communication has not yet been established.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Communication wiring or terminal
resistor connection is faulty, there is
a short circuit, or something is not
connected properly.

Check for wiring errors.
Correct the wiring.
Remove and ground shorts and reconnect loose wires.

Yes

Master-side programming error

Check communications at start-up and correct
programming errors.

Damaged communication circuitry

Perform a self-diagnostics check.
Replace the drive if the fault continues to occur.