6 Related Parameters
6
Related Parameters
The following parameters are used to set up the drive for operation with the option.
Confirm proper setting of parameters in
before starting network communications.
Table 9 Related Parameters
No.
(Addr. Hex)
Name
Description
Values
b1-01
(180)
Frequency Reference
Selection
Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)
Default: 1
Range: 0 to 4
(Set to 3 for
CompoNet only)
b1-02
(181)
Run Command
Selection
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S
2: MEMOBUS/Modbus communications
3: Option PCB
Default: 1
Range: 0 to 3
(Set to 3 for
CompoNet only)
F6-01
(3A2)
Operation Selection
after
Communications
Error
Determines drive response when a bUS error is detected
during communications with the option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Default: 1
Range: 0 to 3
F6-02
(3A3)
External Fault
Detection Conditions
(EF0)
Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation
Default: 0
Range: 0, 1
F6-03
(3A4)
Stopping Method for
External Fault from
Communication
Option
Determines drive response for external fault input (EF0)
detection during CompoNet communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Default: 1
Range: 0 to 3
F6-07
(3A8)
NetRef/ComRef
Selection Function
0: Multi-step speed reference disabled
1: Multi-step speed reference allowed
Default: 1
Range: 0, 1
F6-08
(36A)
Reset
Communication
Related Parameters
Determines which F6- and F7- parameters are
reset to default values when the drive is initialized using
A1-03.
0: Do not reset parameters
1: Reset parameters
Default: 0
Range: 0, 1
F6-40
(3D5)
MAC ID
Selects the drive MAC address
Note: Used in the CompoNet Link Object
Default: 0
Min: 0
Max: 63