beautypg.com

Yaskawa AC Drive Z1000 HVAC User Manual

Page 41

background image

Table i.19 Factory Recommended Z1000 AC Drive Branch Circuit Protection

Model

Nominal Output

Power (HP)

AC Drive Input

(A)

MCCB Rating (A)

<1>

Time Delay Fuse

Rating (A)

<2>

Non-time Delay

Fuse Rating (A)

<3>

Bussmann

Semiconductor

Fuse Model

(Fuse Ampere)

<4>

Three-Phase 200 V Class

2A0011

3

10.6

20

17.5

30

FWH-40B (40)

2A0017

5

16.7

30

25

50

FWH-50B (50)

2A0024

7.5

24.2

40

40

70

FWH-80B (80)

2A0031

10

30.8

60

50

90

FWH-100B (100)

2A0046

15

46.2

90

80

125

FWH-150B (150)

2A0059

20

59.4

110

100

175

FWH-175B (175)

2A0075

25

74.8

150

125

200

FWH-225A (225)

2A0088

30

88

175

150

250

FWH-225A (225)

2A0114

40

114

225

175

300

FWH-250A (250)

2A0143

50

143

250

250

400

FWH-275A (275)

2A0169

60

169

300

275

500

FWH-350A (350)

2A0211

75

211

400

350

600

FWH-400A (400)

2A0273

10

273

500

450

<5>

FWH-450A (450)

2A0343

125

343

600

600

FWH-600A (600)

2A0396

150

396

700

<5>

FWH-600A (600)

Three-Phase 400 V Class

4A0005

3

4.8

15

8

12

FWH-40B (40)

4A0008

5

7.6

15

12

20

FWH-40B (40)

4A0011

7.5

11

20

17.5

30

FWH-45B (45)

4A0014

10

14

25

20

40

FWH-45B (45)

4A0021

15

21

40

35

60

FWH-60B (60)

4A0027

20

27

50

45

80

FWH-60B (60)

4A0034

25

34

60

50

100

FWH-125B(125)

4A0040

30

40

75

70

110

FWH-150B (150)

4A0052

40

52

100

90

150

FWH-200B (200)

4A0065

50

65

125

110

175

FWH-225A (225)

4A0077

60

77

150

125

225

FWH-225A (225)

4A0096

75

96

175

150

275

FWH-225A (225)

4A0124

100

124

225

200

350

FWH-250A(250)

4A0156

125

156

300

250

450

FWH-300A (300)

4A0180

150

180

350

300

500

FWH-350A (350)

4A0240

200

240

450

400

<5>

FWH-400A (400)

4A0302

250

302

600

500

FWH-600A (600)

4A0361

300

346

600

600

1000

<6>

FWH-800A (800)

4A0414

350

410

800

700

1200

<6>

FWH-800A (800)

4A0480

400

480

900

<5>

<5>

FWH-700A (700)

4A0590

500

590

1100

FWH-1000A

(1000)

<1> Maximum MCCB rating is 15 A, or 200% of drive input current rating, whichever value is larger. MCCB voltage rating must be 600 Vac or greater.
<2> Maximum Time delay fuse is 175% or drive input current rating. This covers any Class J, T, or CC fuse.
<3> Maximum Non-time delay fuse is 300% of drive input current rating. This covers any Class J, T, or CC fuse.
<4> When using semiconductor fuses, Bussmann FWH fuses are required for UL compliance.
<5> Consult factory.
<6> Class L fuse is also approved for this rating.

i.5 UL/cUL Standards

YASKAWA ELECTRIC TOEP YAIZ1U 01A YASKAWA AC Drive – Z1000 Safety Precautions

41