Damper/BAS Interlock Circuit Installation
When a Run command is received in HAND or AUTO mode, the E7 Electronic Bypass will display a red "Damper/BAS"
LED in the System Status area of the front control panel. This condition will prevent Drive or Bypass operation.
Figure 5
Figure 5 Damper BAS Interlock LED Indication
Installing or Deactivating the Damper/BAS Interlock Circuit
One of these three actions below must be taken prior to equipment start-up to prevent the Damper/BAS Interlock
condition.
1. Option 1: Install a normally closed (N.C.) BAS Interlock Circuit between TB1-3 and TB1-9 on PCB A2.
Refer to
.
2. Option 2: Install a jumper between TB1-3 and TB1-9 on PCB A2 according to
This method should be
used if a BAS Interlock Circuit will be added later in the installation.
3. Option 3: De-activate terminal TB1-3 by moving DIP switch S2-8 to the ON position (toward the enclosure door).
Refer to
. This solution is only suggested if a BAS Interlock Circuit will never be applied to the drive system
.
Figure 6
Figure 6 Option 1: Normally Closed (N.C.) Damper/BAS interlock Installation