Yaskawa G5 PID for Trim Control User Manual

Page 7

background image

Date: 07/01/04, Rev: 04-07

Page 7 of 12

TM.G5SW.012


This Table Replaces A Portion Of Table A1-2

(2)

Availability

(4)

Parameter

Number

Function

Name

Description

Incre-

ment

Setting

Range

Factor

y

Setting

0 1 2 3

Modbus

Address

b5-01

PID Control

Mode

Selection

0: Disabled
1: PID Output Only
2: PID + Reference
3: Accel/Decel Time Change

1

0 - 3

0

A A A

A

194H

b5-02

PID

Proportional

Gain

0.01

0.00 -
25.00

1.00 A

A

A

A

195H

b5-03

PID Integral

Time

0.1

sec

0.0 -

360.0

1.0 A

A

A

A

196H

b5-04

PID Integral

Limit

0.1%

0.0 -

100.0

100.0 A A A

A

197H

b5-05

PID

Differential

Time

0.01

sec

0.00 -
10.00

0.00 A

A

A

A

198H

b5-06

PID Output

Limit

0.01%

0.00 -

100.00

100.00 A A A

A

199H

b5-07

PID Position

Offset

0.01

V

-10.00 -

+10.00

0.00 A

A

A

A

19AH

b5-08

Accel/Decel

Switching

Delay

0.01

sec

0.00 -
10.00

0.00 A

A

A

A

19BH

b5-09

PID Output

Select

0: Not Inverted
1: Inverted

1

0 - 1

0

A A A

A

589H

b5-10

PID Position

High

0.01

V

-10.00 -

+10.00

10.00 A A A

A

587H

b5-11

PID Position

Low

0.01

V

-10.00 -

+10.00

0.00 A

A

A

A

588H

b5-12

PID

Hysteresis

0.01

V

0.00 -

1.00

0.10 A

A

A

A

586H

(2)

GPD515/G5 Technical Manual TM4515

(4)

Capability to view and set specific parameters is dependent upon the Access Level (A1-01) and Control Method (A1-

02: 0 = V/f, 1 = V/f w/PG, 2 = Open Loop Vector, 3 = Flux Vector) the drive is programmed for. Each column represents
the minimum Access Level for a given Control Method: 0 = Operation only; Q = Quick-start; B = Basic; A = Advanced; - =
not available.