b5-05: Differential Time 
 
 
 
The differential time can be adjusted to increase system response to fast load or reference changes, and to reduce 
overshoot upon startup. To eliminate the differential function entirely, set this parameter to 0.00 seconds. 
 
b5-06: PID Output Limit 
 
 
This parameter can be used to set the maximum effect of the PID controller will have on the system. This works whether 
the PID controller output is positive or negative. NOTE: When the PID output limit is reached, the integrator will hold and 
not increase in value until the PID output is less than the PID output limit. 
 
 
b5-08: Accel/Decel Switching Delay 
 
 
This parameter sets the amount of time after achieving set speed when the accel/decel ramps will switch between their 
present settings and Accel/Decel 4 (C1-07 & C1-08). When a stop command is given, the Accel/Decel ramps will revert 
to Accel 1 / Decel 1. This feature is only effective when b5-01 = 3. 
 
Timing Chart of Output + Reference, With accel / decel timer (b5-01 = 3)
 
 
 
 
b5-09: PID Output Select 
 
This parameter determines whether the output of the PID controller will be added to or subtracted from the frequency 
reference (only when b5-01 = 2 or 3). 
Setting Description
0
Not Inverted
The output of the PID controller will be added to the frequency reference. This would be used when the 
output voltage or current of the feedback device increases with motor speed. 
1
Inverted
The output of the PID controller will be subtracted from the frequency reference. This would used when 
the output voltage or current of the feedback device decreases with motor speed. 
Factory Setting: 0.00 
Range: 0.00-10.00 seconds 
Factory Setting: 100.00 
Range: 0.00 - 100.00 
Factory Setting: 0.00 
Range: 0.00-10.00 seconds 
Factory Setting: 0 
Range: 0, 1 