Date: 07/01/04, Rev: 04-07

Page 5 of 6

TM.G5SW.022

P1-04

PID Integral Limit

A - - -

PID I Limit

P1-04= 100.0 %


Sets the maximum limit of the accumulated integral error.

P1-05

PID Derivative Time

A - - -

PID D Time

P1-05= 0.00 Sec


Sets the PID response based on how quickly the voltage feedback varies.

P1-06

PID Limit

PID Limit

A - - -

PID Limit

P1-06= 100.0%


Sets the maximum output from the PID.

P1-07 PID

Offset

A - - -

PID Offset

P1-07= 0.0%


This value is added to the PID output.

P1-08

PID Delay Time

A - - -

PID Delay Time

P1-08= 0.00 Sec


Delays the PID output.

P1-09

Vref Accel Time

A - - -

Vref Rate Time

P1-09= 0.20 Sec


Sets the rate that the PID will increase the output voltage.

Setting Range

0.0 to 100.0%

Factory Default: 100.0%
Modbus Address: 0x583

Setting Range

0.00 to 10.00 Seconds

Factory Default: 0.00 Sec
Modbus Address: 0x584

Setting Range

0.0 to 100.0%

Factory Default: 100.0%
Modbus Address: 0x585

Setting Range

0.0 to 100.0%

Factory Default: 0.0%
Modbus Address: 0x586

Setting Range

0.00 to 10.00 Seconds

Factory Default: 0.00 Sec
Modbus Address: 0x587

Setting Range

0.00 to 2.00 Seconds

Factory Default: 0.20 Sec
Modbus Address: 0x588