Yaskawa F7 Drive Output Voltage PID User Manual
Page 8

Date: 05/05/05, Rev: 05-05
Page 8 of 8
TM.F7SW.061
7.0 Typical Parameter Settings
7.1 Parameter Settings for a Typical Power Supply Application (480V Drive).
Parameter
Description
Setting
A1-02
Control Method
0 (V/F Control)
B1-01
Reference Source
0 (Keypad)
B1-03
Stopping Method
1 (Coast to Stop)
B1-04
Reverse Operation
1 (Disabled)
C1-01 Acceleration
Time
1
0.20sec
C1-02 Deceleration
Time
1
0.20sec
C2-01
S-curve Time 1
0.00sec
C2-02
S-curve Time 2
0.00sec
C2-03
S-curve Time 3
0.00sec
C4-01
Torque Compensation Gain
0.00
C6-01
Operation Duty Selection
1 (Normal Duty 1) *3
C6-02
Carrier Frequency Selection
3 (8.0kHz) *3
D1-01
Frequency Reference 1
60.00Hz
E1-03
V/F Pattern Selection
FF (Custom w/o Limit)
E1-05
Maximum Output Voltage
460VAC
H3-05
Terminal A3 Function Selection
20 (Output Voltage Feedback)
L2-01
Powerloss Detection Selection
2 (CPU Ride Through)
L2-03
Minimum Base Block Time
0.1sec
L2-04
Voltage Recovery Ramp Time
0.0sec
L2-05
Undervoltage Detection Level
150VDC *3
L3-01
Stall Prevention During Acceleration
0 (Disabled)
L3-04
Stall Prevention During Deceleration
0 (Disabled)
L3-05
Stall Prevention During Running
0 (Disabled)
L8-05
Input Phase Loss Selection
0 (Disabled)
L8-07
Output Phase Loss Selection
0 (Disabled)
N1-01
Hunting Prevention Selection
0 (Disabled)
N9-10
AVR Time Constant
100.0msec *4
N9-14
Power Factor Detection Time 1
1000.0msec *4
N9-15
Power Factor Detection Time 2
1000.0msec *4
P1-01
Output Voltage PID Setpoint
460VAC
P1-02
Output Voltage PID Gain
3.00
P1-03
Output Voltage PID Integral Time
0.30sec
P1-07
Output Voltage Feedback Scaling (Sensor
Dependent)
VAC
*3: Changing these settings to the values shown may require either a higher capacity drive or additional
hardware. Please consult the Industrial Applications department at Yaskawa before adjusting.
*4: Formerly factory access level parameters. Please consult the Industrial Applications department at Yaskawa
before adjusting.