Yaskawa F7 Drive Output Voltage PID User Manual
Page 5

Date: 05/05/05, Rev: 05-05
Page 5 of 8
TM.F7SW.061
4.1 Parameters (continued)
Control Mode *1
Paramete
r
Numb
er
Modbu
s
Addre
ss
Parameter Name
Digital Operator
Display
Description
Ran
ge
Default
Cha
nge
Duri
ng Run
V/f
V/f w/ P
G
Open Lo
op
Vector
Flu
x
Vector
P2-01 60Ah
RMS Output
Current (Iac)
Compensation
Iac RMS Comp V
Sets the amount of
voltage compensation
when the RMS output
current is 100%.
Note: A setting of 0.0VAC
disables this feature.
0.0 ~
200.0
VAC
0.0 Yes
A - - -
P2-02 60Bh
Output Current
(Iac)
Compensation
Filter Time
Iac RMS FiltTime
Sets the 1
st
order filter
time on the RMS output
current (Iac)
compensation feedback.
A smaller setting equals
more response but less
stability.
0.01 ~
1.00
sec
0.01 Yes A - - -
P2-03 60Ch
Iq Voltage
Compensation
Iq Comp V
Sets the amount of
voltage compensation
when the secondary
current is 100%.
Note: A setting of 0.0VAC
disables this feature.
0.0 ~
200.0
VAC
0.0 Yes
A - - -
P2-04 60Dh
Iq Voltage
Compensation
Filter Time
Iq Filt Time
Sets the 1
st
order filter
time on the secondary
current (Iq) compensation
feedback. A smaller
setting equals more
response but less
stability.
0.01 ~
1.00
sec
0.01 Yes A - - -
*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”.