Devicenet™ with adr option kit cm012 – Yaskawa DeviceNet with ADR Option Kit CM012 User Manual
Page 4

Yaskawa Electric America, Inc. –
www.yaskawa.com
IG.AFD.16, Page 4 of 7
Date: 06/15/2007 Rev: 07-06
DeviceNet™ With ADR Option Kit
CM012
13. Yaskawa Supported Input Instances
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
23 (17h)
Extended
Speed and
Torque
Control
6 Bytes
0
–
Network
Reference
1
Network
Run
Command
1
–
–
Fault Reset
Run Reverse
Run Forward
1
Reserved
2
Speed Reference (Scaled by Parameter o1-03) (U1-01)
3
4
Torque Reference (0.1%) (FVC Mode Only, A1-02 = 3) (U1-09)
5
Note:
1
Not available for G5
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
100 (64h)
Modbus
Message
5 Bytes
0
Function Code (Only Modbus functions register read (03h) and register write (10h) are supported)
1
Register Number
2
3
Data
4
Note:
Refer to output assembly instance 150 (96h) for response.
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
101 (65h)
Standard
Control
8 Bytes
0
Terminal S8
1
Terminal S7
Terminal S6
Terminal S5
Terminal S4
Terminal S3
Terminal S2
Terminal S1
1
Terminal
M5-M6
Terminal
M3-M4
Terminal
M1-M2
–
–
–
Fault Reset
External Fault
2
Speed Reference (Scaled by Parameter o1-03) (U1-01)
3
4
Torque Reference (0.1%) (FVC Mode Only, A1-02 = 3) (U1-09)
5
6
Torque Compensation (0.1%) (FVC Mode Only, A1-02 = 3)
7
Note:
1
G5, F7, and G7 Only
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
105 (69h)
Enhanced
Control/
Modbus
Message
8 Bytes
0
Terminal S8
1
Terminal S7
Terminal S6
Terminal S5
Terminal S4
Terminal S3
Terminal S2
Terminal S1
1
Terminal
M5-M6
Terminal
M3-M4
Terminal
M1-M2
–
Function Bit 2
2
Function Bit 1
2
Fault Reset
External Fault
2
Speed Reference (Scaled by Parameter o1-03) (U1-01)
3
4
Register Number
5
6
Data
7
Notes:
Refer to output assembly instance 155 (9Bh) for response.
1
G5, F7, and G7 Only
2
Bit 1
Bit 2
Function Description
0
0
No Function
0
1
Read Register
1
0
Write Register
1
1
No Function