beautypg.com

Wiring – Yaskawa AO-12B2 User Manual

Page 8

background image

Page 8

VS-616/676 Series Option Instruction Manual: Isolated Analog Monitor Card AO-12B2

WIRING

Refer to the following table for the external terminal designations.

Wiring Connection Notes:

1. To prevent noise, use shielded wire as specified in Fig.4.

2. Separate the power wiring circuits (200VAC or greater) and relay wiring circuits (120VAC) from the

control wires.

3. Wire lengths must be 164 feet (50 meters) or shorter.

4. Connect the AO-12B2 grounding lead wire (E) to the inverter control board’s grounding terminal 12.

5. Applicable wire sizes for terminal block TBI are as listed in the following table.

Stripping TB1 Signal Wires for Connection:

The following shows the correct length of insulation to be stripped in order to connect the wire to the Ter-
minal Blocks TB1 Cable Selection:

1. Cable too heavy exerts pressure on the Option Card and could cause failure.
2. Cable too thin could cause a poor connection or prematurely break or overheat.

Table 2: External Terminal Designations

Terminal Block Symbol

Terminal

Number

Function

TB1

1

Isolated Monitor Output Channel 1 (+)

2

Isolated Monitor Output Channel 2 (+)

3

Common Monitor Output (-)

Table 3: Wire Sizes

Type

[mm

2

]

AWG

I[A]

VAC[V]

Thin twisted wire

1

16

12

125

Solid Wire

1.5

16

12

125

UL

--

22-16

10

300

CSA

--

28-16

10

300

CSA

--

28-16

10

150

5.5mm

Fig.5 Terminal Block TB1 Side for Connecting Wire End

This manual is related to the following products: