PROGRAMMING PARAMETER SETTINGS
Note: Refer to “OUTPUT SIGNAL LEVEL SETTING” for 100% output signal level in output
Table 7: Programming Settings With VS-616G3
Terminal
Program
Parameter
Number
Set
Value
Output Contents
Output
Accuracy
TB1-1
Channel 1
Sn-28
1st/2nd
digit
00
Output frequency:
Max. frequency/100%
1.0%
01
Output current:
Inverter rated
voltage/100%
3.0%
TB1-2
Channel 2
Sn-28
1st/2nd
digit
10
Output voltage reference
Input voltage/100%
1.5%
11
DC voltage (V
PN
)
400V/100% (200Vclass)
800V/100% (400Vclass)
1.5%
Program the output terminal to the desired signal using the parameters in the following tables:
Table 7:
Programming settings with G3
Table 8:
Programming settings with H3
Table 9:
Programming settings with G5
Table 10: Programming settings with VG3 or VH3