7 specifications, Revision history, 7specifications – Yaskawa 120 Vac Digital Input User Manual
Page 22

22
YASKAWA TOEP YEAOPT 07 A1000 Option DI-101 120 Vac Interface Installation Manual
7 Specifications
7
Specifications
Table 5 Option Specifications
Revision History
Revision dates and manual numbers are located on the bottom of the back cover.
Specification
Data
Inputs
8 Digital Inputs , +2 Neutral Common
Input Impedance
10 Kohms
On-State Voltage
93 to 132 Vac (110/120 Vac +10 % / -15 %)
On-State Current, Nominal
12.5 mA @ 120 Vac
Off-State Voltage, Maximum
19 Vac
Off-State Leakage Current, Maximum
4.0 mA
Operating Frequency
57 to 63 Hz (+/- 15 %)
On-State Response Time, Maximum
50 ms
Off-State Response Time, Maximum
50 ms
Terminal Wiring
16 AWG to 26 AWG
Area of Use
Indoors
Operating Temperature
-10 to +60 degrees C
Storage Temperature
-20 to +85 degrees C
(short-term temperature during transport)
Humidity
95% Relative Humidity or less (non condensing)
Date of
Publication
Revision
Number
Section
Revised Content
May 2011
−
−
First edition
MANUAL NO.
TOEP YEAOPT 07
Published in USA May 2011 11-5
Date of publication
Date of original publication
Revision number
1