beautypg.com

5 installation procedure – Yaskawa 120 Vac Digital Input User Manual

Page 17

background image

5 Installation Procedure

YASKAWA TOEP YEAOPT 07 A1000 Option DI-101 120 Vac Interface Installation Manual

17

6.

Prepare the external 120 Vac control circuit wires (customer supplied) for terminals
S1 to S8 and X2 on the DI-101 option as shown in

Figure 7

.

Figure 7

Figure 7 Preparing Cable Wiring

7.

Connect the customer wiring to the DI-101 option terminal block. Refer to

Figure 8

for a wiring diagram example showing customer interface circuitry.

Refer to Wire Gauges, Tightening Torques, and Crimp Terminals on page 20

to

confirm that the proper tightening torque is applied to each terminal. Take particular

precaution to ensure each wire is properly connected and wire insulation is not

accidentally pinched into electrical terminals.

WARNING! Fire Hazard. Tighten terminal screws to the specified tightening torque. Loose electrical

connections could result in death or serious injury by fire due to overheating. Tightening screws beyond the

specified tightening torque may cause erroneous operation, damage the terminal block, or cause a fire.

S1S2 S3 S4

X2

X2

S8

S7

S6

S5

DI-101 Option Terminal Block

Preparing wire ends:

Screwdriver blade size

about 5.5 mm (7/32”)
When not using
crimped insulated
sleeves

Strip wire insulation about 5.5 mm
and lightly twist the end with fingers,
keeping the ends from fraying.

Customer-supplied

120 Vac control circuit wires

(do not solder ends)

Loosen the screws and
insert the wire into the
opening on each terminal.

Blade depth of
0.4 mm or less

Blade width of
2.5 mm or less

This manual is related to the following products: