beautypg.com

4 ac connection, 1 check connection requirements – SMA SI 3324 Errata User Manual

Page 9

background image

SMA Solar Technology AG

Electrical Connection

Installation Guide

9/16

SI3324_4248-E-IEN094410

1.4 AC Connection

Connect the Sunny Island through a sub-distribution to the stand-alone grid (loads, PV generator
(Sunny Boy), wind turbine system (Windy Boy) and to any other external sources (generator, grid)).

1.4.1 Check Connection Requirements

Grounding

Provide the protective conductor with with suitable cable end sleeves and connect to the PE terminals
in the AC connection area of the Sunny Island.

Fusing of the Sub-distribution

Use cables with a maximum cross-section of 16 mm² for the AC installation The AC nominal current
is 14 A for the Sunny Island 3324 and 18 A for the Sunny Island 4248.

TN system
When working with public grids, the Sunny Island may only be installed as a TN system.
In stand-alone configurations, the (protective) ground of the Sunny Island and its individual
components must be wired as a TN system only.
All valid standards and guidelines must be taken into account.

CAUTION!
Risk of injury due to high discharge currents against PE.

The N cable of the Sunny Island has NOT been connected with PE by default.

• Ground the stand-alone grid system on the AC side before commissioning outside of

the Sunny Island.

• For safety reasons (discharge currents exceeding 3.5 mA), use either two protective

conductors (redundant grounding) or a protective conductor of at least 10 mm².

DANGER!
Danger to life due to residual currents.

• Protect all users with a residual current breaker (RCD) or, for the Sunny Island 4248,

protect with a 16 A circuit breaker with B tripping characteristic.

No all-pole isolator
The Sunny Island is not disconnected on all poles: the neutral conductor (N conductor) is
looped through the device and the N connection terminals of "AC output" and "AC input"
are connected inside the device.

This manual is related to the following products: