1.4.2 Connecting the AC Output

Connect, with three wires via the sub-distribution, for example, loads, PV generators (Sunny Boy) and
wind turbine systems (Windy Boy), to the Sunny Island's AC output (C) connection.

1. Assemble metric-thread cable screw connections on enclosure opening C (see diagram on

page 3).

2. Thread the three-wire AC cable through the terminal.
3. Provide the three wires of the AC cable with suitable cable end sleeves.
4. Connect PE, N and L cables according to the labeling in the AC output terminal (torque 2.0 Nm

to 4.0 Nm).
L and N must not be swapped.

5. Tighten the counter nut of the metric-thread cable screw connection.

☑ The AC output of the Sunny Island is installed.

Cable Protection
SMA Solar Technology recommends the use of a line circuit breaker (B type, max. 16 A).
This has the following advantages:

• The cable cross-section is dimensioned based on the value of 1 x nominal current.
• For maintenance work, the Sunny Island can be switched off via the line circuit

breaker on the stand-alone grid side.

Position