beautypg.com

2 disassembling the panels – SMA SC 500HE-20 Maintenance Manua User Manual

Page 19

background image

SMA Solar Technology AG

6  Maintenance Under Voltage-Free Conditions

Maintenance Manual

SC500-800HE20-WH-en-10

19

8. Switch off the miniature circuit-breaker of the grid

monitoring.

9. Ensure that all poles are dead.

10. Earth and short-circuit.
11. Cover or safeguard any adjacent live components.
12. Wait 12 minutes for the capacitors to discharge.

6.2 Disassembling the Panels

2. Remove the panel screws using a Torx screwdriver.
3. Loosen the earthing cables of the panels.
4. Remove the panels.

5. Remove protective covers.

6. Ensure that no voltage is present:

• AC connection lugs
• DC connection lugs/DC busbars/DC terminals

1.

%"/(&3

Danger to life from electric shock or electric arc when touching live components.

• Disconnect the inverter (see Section 6.1).