beautypg.com

SMA SMB User Manual

Page 31

background image

SMA Solar Technology AG

10  Technical Data

Installation Manual

SMB-IA-en-10

31

Maximum
operating
current per
measuring
input with
200 A
LV/HRC fuse

130 A

DC input
Screws for fuse
holders

M 10

M 10

M 10

M 10

Torque

30 Nm … 35 Nm 30 Nm … 35 Nm 30 Nm … 35 Nm 30 Nm … 35 Nm

Cable gland

8 x M40

Sealing range

14 mm … 28 mm

Seal insert pre-
mounted

14 mm … 18 mm

Seal insert
included in
scope of
delivery

7 mm …

20.5 mm /

20 mm … 25 mm /

24 mm … 28 mm

Maximum
cable cross-
section

240 mm

2

240 mm

2

240 mm

2

240 mm

2

DC output
Diameter of
through-hole in
busbar

3 x 13 mm

2 x 3 x 13 mm

2 x 2 x 2 x 13 mm 2 x 2 x 2 x 13 mm

Maximum
cross-section
of standard
terminal lug

240 mm

2

240 mm

2

240 mm

2

240 mm

2

Screws
included in
scope of
delivery

3 x M12 /

2 x M12*

2 x 3 x M12

2 x 2 x 2 x M12

2 x 2 x 2 x M12

Torque

74 Nm

74 Nm

74 Nm

74 Nm

Sunny Main Box Sunny Main Box

Cabinet

Sunny Main Box
Cabinet

Sunny Main Box
Cabinet

Option

8 inputs

2 x 8 inputs

2 x 2 x 4 inputs

2 x 2 x 3 inputs