SMA SUNNY CENTRAL Maintenance manual User Manual
Page 60

Maintaining the Sunny String-Monitor-Cabinet
SMA Solar Technology AG
60
SCWAR-WEN094020
Maintenance Manual
9. Check all power cable connections for looseness and tighten them if necessary. Check the
connectors and insulation for discoloration or degradation. Replace any damaged connectors
or corroded contacts.
10. Check all string cable connections for looseness and tighten them if necessary. Check the
insulation, and the terminals on the assembly as well on the busbar for discoloration or
degradation.
11. Check all cable connections of the optional DC main switch for looseness and tighten them if
necessary. Check the insulation and the switch for discoloration or degradation.
12. Check the shield connection of the communication cables. The shield connection must only be
hand-tightened.
13. Check the ground connection and the contact resistance to the ground potential.
14. Check the overvoltage protector. The visual display must be green.
15. Check the filter pads of the ventilation grids for dirt and clean or replace them, if necessary.
Replacement filter pads can be ordered from SMA Solar Technology AG.
☑ Maintenance of the Sunny String-Monitor-Cabinet is completed.