3 country-specific parameter settings, 4 non-modifiable parameters, Country-specific parameter settings – SMA SB 4200TL HC Multi-String User Manual
Page 43: Non-modifiable parameters

SMA
Technologie AG
Technical Data
Installation Guide
SBTLHCMS-IEN080411
Page43
8.4. 3 Country-specific Parameter Settings
The parameters listed below represent country-specific settings and are only displayed
in installer mode. All other parameters are international and can be viewed in the table
in section 8.4. 2.
8.4. 4 Non-modifiable Parameters
The following parameters are displayed in the parameter list but cannot be changed:
Name
Short
descr.
Country settings
Germany
Italy
Great Britain
Default
GER/VDE0126-1-1 IT
GB
dFac-Max Hz/s
4.0
0.20
0.25
dZac-Max mOhm 600
350
350
Fac-delta-
Hz
2.45
0.29
0.5
Fac-delta+ Hz
0.19
0.29
0.5
Ni-Test
1
0
0
T-Start
s
2
2
180
Uac-Min
V
198
198
209
Uac-Max
V
260
260
261
Name
Short
descr.
Factory setting
SB 4200TL HC
SB 5000TL HC
Fac-Tavg
ms
160
160
Firmware-DC-BFR
Hardware-DC-
BFR
Plimit
W
4200
5100
SMA-SN
Software-BFR
Software-SRR
Uac-Tavg
ms
80
80