2 parameter settings for germany, Parameter settings for germany – SMA SB 4200TL HC Multi-String User Manual
Page 41

SMA
Technologie AG
Technical Data
Installation Guide
SBTLHCMS-IEN080411
Page41
8.4. 2 Parameter settings for Germany
Grayed out parameters are only displayed in installer mode. The table below contains
the parameters that are applicable in Germany. The Sunny Boys were prepared for the
DIN VDE 0126-1-1 in two steps. The table specifies the settings that are respectively
valid.
Uac-Tavg
Averaging time of grid frequency gaging
Uzwk-Start
The DC voltage required before the Sunny Boy begins feeding
power into the mains supply.
Usoll-Konst A
PV desired voltage for constant operational voltage. These pa-
rameters are only important when the "Betriebsart" parameter is
set to U-konst.
Usoll-Konst B
Name
Short
descr.
Value range
Factory setting
ACVtgRPro
V
230 ... 300
253
AntiIsland-Ampl *
grd
0 ... 10
0
AntiIsland-Freq *
mHz
0 ... 2000
500
Betriebsart
MPP, IKonst, UKonst,
Stopp,
MPP
Default *
GER/VDE0126-1-1,
IT/DK5950, Other,
trimmed
GER/VDE0126-1-1
dFac-MAX *
Hz/s
0.1 ... 4.0
4.0
dZac-MAX *
mOhm
350 ... 20000
600
E_Total
kWh
0 ... 200000
0
Fac-delta- *
Hz
0.1 ... 4.5
2.45
Fac-delta+ *
Hz
0.1 ... 4.5
0.19
h_Total
h
0 ... 200000
0
Inst.-Code
LDVtgC
V
0 ... 50
0
Ni-Test *
0 / 1
1
Ripple-Ctl-Frq
Hz
110 ... 1605
1605
Ripple-Ctl-Lev
%
0.5 ... 8.00
8
Name
Explanation