beautypg.com

SMA RS485-Quick Module V.3.0 User Manual

Page 2

background image

MUltI-fUnCtIon RElay ConnECtIon

ConnECtIon to thE RS485 bUS

Preparing the cable

1.

Use a cable with a cross-section of 6 to 7 mm.

2.

Remove 40 mm of cable sheath.

3.

Shorten the cable shield to 15 mm and fold it back.

4.

Cut off unused insulated conductors at the cable sheath to prevent a short-circuit.

You need 3 insulated conductors, 2 of them have to be twisted (see "Connecting the

RS485 bus cable" step 9).

5.

Strip 6 mm off the insulated conductors.

6.

Cover the shield with the delivered conductive

adhesive foil.

Preparing the RS485-Quick Module

1.

Open the lid of the RS485-Quick Module.

2.

Loosen the screw of the strain-relief and remove the

jumper.

3.

Remove the filler plugs from the right cable entry (if you

want to connect 2 cables, remove both filler plugs).

4.

Remove the cable support sleeve.

Connecting the RS485 bus cable

5.

Insert the cable and guide it through the cable entry into

the RS485-Quick Module.

6.

Reattach the cable support sleeve.

7.

Push the cable into the shielding clamp.

8.

If one cable is connected (inverter at the end of the

RS485 bus) leave the resistor connected. If the resistance

is not correctly connected, see RS485 cabling plan

poster.

If 2 cables are connected (inverter in the middle of the

RS485 bus), remove the left resistor of the termination

plug.

9.

Connect the insulated conductors to the string-type

terminals and make a note of the color of the insulated

conductors.

Signal RS485-Quick Module Insulated conductor

color

RS485 bus

5

5

Data+

2

2

Data-

7

7

10.

Reattach the jumper and fasten the screw of the strain-

relief.

11.

Close the lid and flip the flap down again until it locks

into place.

12. Connect the other end of the cable to the RS485 bus node. See the supplied RS485

cabling plan poster for the connection layout and system wiring.

The RS485-Quick Module is connected to the RS485 bus.

Connection requirements

You have the option of connecting separate loads both in the event of failure and for trouble-free

operation.
The following table contains the maximum permissible voltages and currents:

voltage

Current

AC

Max. 240 V

Max. 1.0 A

DC

Max. 30 V

Max. 1.0 A

Cable Requirements

• The cable type and cable-laying method must be appropriate to the application and loca-

tion.

• The cable must be double-insulated.

Position

Description

value

a

External diameter

11.7 mm ... 12.5 mm

b

Cross-section of insulated conductor

0.5 mm² ... 2.5 mm²

C

Length of the insulated conductor

max. 15 mm

D

Strip insulation

max. 8 mm

line circuit breaker

If you connect the multi-function relay to the power distribution grid, the relay must be fused with

an individual line circuit breaker.

Connection plan

Preparing the RS485-Quick Module

1.

Open the lid of the RS485-Quick Module.

2.

Loosen the screw of strain-relief on the right side and

remove the jumper.

Connecting the cable to the multi-function relay

3.

Pierce the seal with a screwdriver or a pointed object

and lead the cable inside.

4.

Connect the insulated conductors to the multi-function

relay as shown in the connection plan, depending

on whether you require an operating or an error

message. Reattach the jumper and fasten the screw

of the strain-relief.

5.

Close the lid and flip the flap down again until it

locks into place.

The multi-function relay is connected.