beautypg.com

SMA METER CONNECTION BOX User Manual

Page 24

background image

Parameter Overview

SMA Solar Technology AG

24

METERBOX-IEN110611

Installation Guide

Information on the Parameter "S0 Pulse/kWh"
This parameter is reset to the value "0" and the Meter Connection Box stops counting if you
select another energy meter type for the adjustable parameter "DeviceType"
(see page 23).

• If you have selected another energy meter type, enter the value for the parameter

"S0 pulse/kWh" that corresponds to the S0 interface of the selected energy meter
(see type label of the selected energy meter).

Information on the Parameter "S0 Offset"
This parameter is reset to the value "0" if you select another energy meter type for the
adjustable parameter "DeviceType" (see page 23). If you wish, enter the meter reading of
the newly selected energy meter type here. If you do not enter the meter reading, the Meter
Connection Box begins to count again with the value "0".