7. In the parameter PwrMonErrTm configure the time lapse until recognition of the absence of setpoint specifications.
8. Confirm the parameter entry with [Save].
8.3.2 No Q at Night: Off Mode
The reactive power setpoint is limited to 0 kVAr. This setpoint cannot be controlled.
8.3.3 Q at Night with Setpoint Command via Modbus Protocol: VArCtlCom Mode
The reactive power setpoint is received via the Power Reducer Box or the Power Plant Controller. The setpoint is
transmitted as a percentage and converted to kVAr in the device.
If the Sunny Central has not received any signal for the last five minutes, the error message Q-VArModFailStt will be
displayed (see Section 8.2.2, page 63).
8.3.4 Q at Night with Absolute Value: VArCnst Mode
The reactive power setpoint is set using the parameter QoDQ-VAr. Note that the permitted range for the parameter
QoDQ-VAr is ‒QoDQmax to +QoDQmax.
8.3.5 Q at Night as a Percentage of the Nominal Power: VArCnstNom Mode
The parameter QoDQ-VArNom is used to set the reactive power setpoint in %. The parameter QoDQ-VArNom refers
to Pmax. If the calculated amount of reactive power exceeds the predefined value of QoDQmax, the power will be
limited to QoDQmax. If the calculated amount of reactive power falls below the predefined value of ‒QoDQmax,
the power will be limited to ‒QoDQmax.
8.3.6 Q at Night via Standard Signal: VArCnstNomAnIn Mode
The reactive power setpoint is set via an analog signal at the input terminals for setpoint specification (see Sunny Central
installation manual). This is usually implemented by a ripple control signal.
The analog value is converted into a reactive power setpoint. The electrical current strength of the connected signal
determines the setpoint.
The analog measured values must be between 4 mA and 19 mA. If the analog signal is less than 2 mA, an error message
will be displayed in the instantaneous value Q-VArModFailStt (see Section 8.2.2, page 63).
The analog value is converted to a setpoint for power limitation. Here, the parameter QoDQmax is the end point of the
linear characteristic curve.
PF-PFSubVal
Proxy value for the displacement power factor outside of feed-in operation
PF-PFExtSubVal
Proxy value for the excitation of the displacement power factor outside of feed-in operation
Signal
Power limit
Description
< 2 mA
Last valid value or 0 kVAr
after restart
Signal is in the invalid range.
2 mA to 4 mA
− Pmax
The maximum amount of negatively excited reactive power is fed in.
4 mA
− Pmax
Start point of the characteristic curve
The maximum amount of negatively excited reactive power is fed in.
11.5 mA
0 kVAr
Zero-crossing of the characteristic curve
No reactive power is fed in.
> 19 mA
+Pmax
End point of the characteristic curve
The maximum amount of positively excited reactive power is fed in.