SMA Solar Technology AG

Sealing

Additional sheet

Plomb-BB-IEN112920

2/6

3 Sealing

3.1 Requirements for sealing

☐ The sealing wires are provided by the customer.
☐ The seals are provided by the electric utility company.
☐ The central inverter is disconnected.

3.2 Sealing the front side of the connection cabinet

Figure 1: Positions of the screws for sealing (in this example a Sunny Central 500CP)

1. Remove the screws from the front and side panels using a Torx screwdriver. Put the washers

safely to one side.

2. Insert the sealing screws with washers and tighten (torque 6 Nm).
3. Thread the sealing wire through the screw pairs.
4. Seal the sealing wire using the seal.

8"3/*/(

Risk of death due to electric shock when live component parts of the central inverter are
touched!

• Disconnect the central inverter before sealing.

Position

Description

A

1st pair of screws

B

2nd pair of screws

C

3rd pair of screws