beautypg.com

1 cable requirements, Cable requirements – SMA SBCBTL6 User Manual

Page 33

background image

SMA America, LLC

Technical Data

Installation Guide

SBCBTLUS-IUS094510

33

11.1 Cable requirements

Use only 194 °F (90 °C) copper wire for all DC wiring connections to the screw terminals between

• PV modules and Sunny Boy Combiner Box
• Sunny Boy Combiner Box and Sunny Boy

Connection - Sunny Boy Combiner Box

The conductor cross-section must be adjusted to the maximum current.

*The listed terminals are rated to a temperature of +221 °F (+105 °C).

Terminal

Torque

Wire Size

String Inputs*

15 in-lbs. (1.7 Nm)

14 AWG … 6 AWG (2.5 mm² … 16 mm²)

Combined Out*

40 in-lbs. (4.5 Nm)

6 AWG … 2 AWG (16 mm² … 35 mm²)

Equipment grounding*

40 in-lbs. (4.5 Nm)

8 AWG … 2 AWG (10 mm² … 35 mm²)