EMI UNH-T2H-T3H-T4H User Manual
Page 5
Rome, New York, USA
Enviromaster International LLC
5
interconnecting tUBing sPecifications
Indoor
Unit
Outdoor
Circuit
Capacity
maximum Separation,
Equivalent ft (m)
maximum Elevation
Difference
ft (m)
Liquid
Line OD
Suction
Line OD
Condensate
Line ID
UNH09
9,000 Btuh
100 (30.5)
35 (10.7)
1/4”
1/2”
1/2”
UNH12
12,000 Btuh
100 (30.5)
35 (10.7)
1/4”
1/2”
1/2”
UNH24
18,000 Btuh
100 (30.5)
35 (10.7)
3/8”
5/8”*
1/2”
UNH24
24,000 Btuh
100 (30.5)
35 (10.7)
3/8”
3/4”
1/2”
* UNH24 Suction Connection size is 3/4” O.D. and must bush down at the UNH Unit.
Manufacturer reserves the right to change these specifications at any time without incurring obligation.
indoor air floW
Indoor Unit
CFm (l/s)
Coil
ft/min (m/s)
Air throw, ft. (m)
High Speed
Low Speed
UNH09
or
UNH12
425 (200)
375 (175)
Dry
900 (4.6)
15 (4.6)
UNH24
700 (350)
550 (250)
1,225 (6.2)
24 (7.3)
soUnd data
Unit
Sound dbA
UNH09 or UNH12
51
UNH24
56
T2H
70
T3H
70
T4H
70
Note: Sound data for indoor unit at high speed, 230 V
Sound data for outdoor unit at 230V
WeigHt data
Unit
Weight, lbs (kg)
UNH09
92 (41.8)
UNH12
95 (43.2)
UNH24
116 (52.7)
T2H
325 (147.7)
T3H
325 (147.7)
T4H
325 (147.7)
EmI ENGINEERING SUbmIttAL UNH-t2H-t3H-t4H
Outdoor
Unit
Power Supply
V-1-60
Control*
V-1-60
Compressor
Outdoor Fan motor Unit
FLA mCA mOCP
Volts
min
max
Qty RLA LRA Qty FLA
Hp
T3H2240
208/230
197
240
24
2
4.3 27.0
1
1.8
0.33
19.2
21.4
30
1
8.8 54.0
T3H2220
208/230
197
240
24
3
4.3 27.0
1
1.8
0.33
14.7
15.8
20
T4H9999
208/230
197
240
24
4
3.4 23.0
1
1.8
0.33
15.4
16.3
20
T4H9992
208/230
197
240
24
3
3.4 23.0
1
1.8
0.33
16.3
17.4
20
1
4.3 27.0
T4H9922
208/230
197
240
24
2
3.4 23.0
1
1.8
0.33
17.2
18.3
20
2
4.3 27.0
T4H9222
208/230
197
240
24
1
3.4 23.0
1
1.8
0.33
18.1
19.2
20
3
4.3 27.0
T4H2222
208/230
197
240
24
4
4.3 27.0
1
1.8
0.33
19.0
20.1
25
Note: * - Control Voltage is supplied from the indoor unit. No separate supply required.
electrical sPecifications