EMI UNH-T2H-T3H-T4H User Manual

Page 5

background image

Rome, New York, USA

Enviromaster International LLC

5

interconnecting tUBing sPecifications

Indoor

Unit

Outdoor

Circuit

Capacity

maximum Separation,

Equivalent ft (m)

maximum Elevation

Difference

ft (m)

Liquid

Line OD

Suction

Line OD

Condensate

Line ID

UNH09

9,000 Btuh

100 (30.5)

35 (10.7)

1/4”

1/2”

1/2”

UNH12

12,000 Btuh

100 (30.5)

35 (10.7)

1/4”

1/2”

1/2”

UNH24

18,000 Btuh

100 (30.5)

35 (10.7)

3/8”

5/8”*

1/2”

UNH24

24,000 Btuh

100 (30.5)

35 (10.7)

3/8”

3/4”

1/2”

* UNH24 Suction Connection size is 3/4” O.D. and must bush down at the UNH Unit.

Manufacturer reserves the right to change these specifications at any time without incurring obligation.

indoor air floW

Indoor Unit

CFm (l/s)

Coil

ft/min (m/s)

Air throw, ft. (m)

High Speed

Low Speed

UNH09

or

UNH12

425 (200)

375 (175)

Dry

900 (4.6)

15 (4.6)

UNH24

700 (350)

550 (250)

1,225 (6.2)

24 (7.3)

soUnd data

Unit

Sound dbA

UNH09 or UNH12

51

UNH24

56

T2H

70

T3H

70

T4H

70

Note: Sound data for indoor unit at high speed, 230 V

Sound data for outdoor unit at 230V

WeigHt data

Unit

Weight, lbs (kg)

UNH09

92 (41.8)

UNH12

95 (43.2)

UNH24

116 (52.7)

T2H

325 (147.7)

T3H

325 (147.7)

T4H

325 (147.7)

EmI ENGINEERING SUbmIttAL UNH-t2H-t3H-t4H

Outdoor

Unit

Power Supply

V-1-60

Control*

V-1-60

Compressor

Outdoor Fan motor Unit

FLA mCA mOCP

Volts

min

max

Qty RLA LRA Qty FLA

Hp

T3H2240

208/230

197

240

24

2

4.3 27.0

1

1.8

0.33

19.2

21.4

30

1

8.8 54.0

T3H2220

208/230

197

240

24

3

4.3 27.0

1

1.8

0.33

14.7

15.8

20

T4H9999

208/230

197

240

24

4

3.4 23.0

1

1.8

0.33

15.4

16.3

20

T4H9992

208/230

197

240

24

3

3.4 23.0

1

1.8

0.33

16.3

17.4

20

1

4.3 27.0

T4H9922

208/230

197

240

24

2

3.4 23.0

1

1.8

0.33

17.2

18.3

20

2

4.3 27.0

T4H9222

208/230

197

240

24

1

3.4 23.0

1

1.8

0.33

18.1

19.2

20

3

4.3 27.0

T4H2222

208/230

197

240

24

4

4.3 27.0

1

1.8

0.33

19.0

20.1

25

Note: * - Control Voltage is supplied from the indoor unit. No separate supply required.

electrical sPecifications

continued