2 installation, Figure 14 – ups ratings – Energy Tech Laboratories EDP70 User Manual
Page 21
MI00/10056 rev.1--05/2001-- page
21
4.2
Installation
Check the rating label on the rear of the front panel of the EDP70 PLUS UPS to ensure the input/output voltages,
frequency and load are all within the rating of the UPS.
EDP70 PLUS is designed to operate in an office environment with an optimum temperature of 68
°
F [20 C].
A gap of at least 4In [ 10cm. ] must be maintained at rear of the UPS to ensure adequate ventilation.
Nothing should be placed around the equipment which might restrict the airflow.
Ensure the interconnecting cables do not cause a hazard to the user.
A gap of at least 32 In [ 800 mm] must be maintained above the UPS to ensure adequate space for maintenance.
The appropriate lifting equipment must be used to move the EDP70 PLUS UPS.
Figure 14 – UPS Ratings
UPS ratings
Description
U.M.
24
12kVA
24
18kVA
24
24kVA
36
24kVA
36
30kVA
36
36kVA
Output power
kVA
12
18
24
24
30
36
Nominal Load
kW
8
12
16
16
20
24
Maximum input power (with
unit @ nominal Load &
battery recharge)
kVA
15
21
28
28
35
42
Maximum dissipation (with
inverter @ nominal Load)
BTU/H
3750
5460
6800
7700
9500
11300
Number of battery cells
n
144
240
Battery voltage range
V
238-327
396-545
Battery
end-discharge current
A
37
55
74
53
67
80
UPS ratings
Description
U.M.
50
30kVA
50
40kVA
50
50kVA
80
50kVA
80
65kVA
80
80kVA
Output power
kVA
30
40
50
50
65
80
Nominal Load
kW
24
32
40
40
52
64
Maximum input power (with
unit @ nominal Load &
battery recharge)
kVA
43
57
71
71
91
112
Maximum dissipation (with
inverter @ nominal Load)
BTU/H
14300
14300
18600
22100
Number of battery cells
n
240
Battery voltage range
V
396-545
Battery
end-discharge current
A
67
88
110
105
140
173