BYPASSING & ISOLATING

(continued)

3---4

4. Open the lower enclosure door. Pull out both left and

right side rails then use the two tab handles to roll out
the transfer switch. It can be safely inspected in this
position. The transfer switch can also be removed for
easier maintenance operations. See Figure 3–13.

Hazardous voltage capable of causing

electrical shock, burns, or death;

do not touch any control circuit terminals.

right rail

left rail

tab

handles

Figure 3–13.Transfer switch isolated

and pulled out for inspection.

See page 2–2 for maintenance handle use. A lifting yoke

812053 is available to facilitate lifting by using an

overhead crane or similar equipment. See WARNING.

The Transfer Switch weighs about 150 lbs.

depending upon the number of poles. Use lifting

device 812053 or other device capable of lifting

this weight to avoid personal injury or equipment

damage. Two persons are recommended.

Contact Inspection

Contact condition should be checked annually.

Discoloration is normal. Do not file contacts

because it wastes material. Instead use light emery

paper to clean up the contact surfaces. The

non–replaceable main contacts are designed to last

the life of the transfer switch.

To prevent the possibility of fatal electrical

shocks and burns, bypass, isolate, and withdraw

the transfer switch before working on it.

1. Deenergize transfer switch (pages 3–1 thru 3–4)

Bypass, isolate, and withdraw transfer switch.

Use a voltmeter to verify that no electrical

power is present at the transfer switch terminals.

2. Use the maintenance handle (page 2–2).

Open the contacts that will be inspected by using

the detachable maintenance handle.

3. Remove the barrier (Figure 3–14).

Use a phillip screwdriver to loosen (ccw) four or

six captive round–head screws holding the

barrier to the arc chutes. Then pull the barrier

straight outward to remove it.

4. Reinstall the barrier.

Install the barrier over the arc chutes. Use a

phillips screwdriver to tighten (cw) the four or six

round–head screws to secure the barrier to the arc

chute insulator nuts. See Figure 3–14.

Figure 3–14. Barrier removal.