Archgard 60-1600I User Manual
Page 8

Chalet 1600I
8
A
B
C
D
E
Hearth Protection
In the USA, the floor protection must be made of non-combustible material and must extend 16" in front and
8” beyond each side of the fuel loading and ash removal openings. Consult with your local inspector/
authority having jurisdiction or check the NFPA 211 or local codes.
In Canada, the floor protection must be made of non-combustible material and must extend 18" (450mm) in
front and 8” beyond each side of the fuel loading and ash removal openings. A 0.38 mm (0.015 in) thick
metal sheet or a grouted ceramic floor-tile surface installed in accordance with recognized Building Codes
shall be considered a durable pad. A floor pad shall not be placed on top of a carpet unless the pad is struc-
turally supported to prevent displacement and distortion. Consult with your local inspector or check the
CSA B365.
All floor protection must be non-combustible (i.e. metals, brick, stone, mineral fiber boards, etc.). Any or-
ganic materials (i.e., plastics, wood paper products, etc.) are combustible and must not be used.
Total =
brick +
mineral board = 0. 8 + 0.431 = 1.231
Step ( c ): Compare proposed system
total of 1.231 to specified R of 0.893. Since proposed system
total is greater than
required , the system is acceptable.
DEFINITIONS:
= ( ft ² )(hr)(°F)
k = K X 12 K= ( ft ² ) (hr) (°F) r =
=
R
R
R
R
R
R
Btu
(Btu) (in)
( ft
(Btu) (ft)
( ft ² ) (hr) (°F)
(Btu) (in)
1
k