AEC WD 350 through WD3000 Dehumidifying Dryers User Manual
Page 44
350-2100 cfm Dryers
Chapter 6: Maintenance
43 of 58
Display
Characters
Sensor Type
Switch
Position
Temp
Range
°C
°F
Thermocouple Type R
0
0 - 1,700
0 - 3,000
Thermocouple Type S
1
0 - 1,700
0 - 3,000
Thermocouple Type K
2
-200 to
1,300
-300 to
2,300
Thermocouple Type J
3
-100 to
900
-100 to
1,600
Thermocouple Type T
4
-200 to
400
-300 to
700
Thermocouple Type E
5
0 to 600
0 to 1,100
Platinum RTD (JIS
1981)
6 -99.9
to
450.0
-99.9 to
800.0
Platinum RTD (DIN)
7
-99.9 to
450.0
-99.9 to
800.0
Not Used
8
Not Used
9
9. Set both transmission output selector DIP switches OFF. They are marked SW207 (TRANSFER)
and are on the right circuit board on controls equipped with optional communications. See the
Communications Manual [part number A0535959].
1
2
3
4
5
6
ON
10. The function selector DIP switch [SW201 (FUNCTION)] selects 6 control modes. It is on the right
circuit board. Put this switch in the set-up configuration at right while inputting the initial control
parameters.
SW201 Set-up Configuration
1 OFF
Control Mode
2 OFF
Normal/Reverse Output
3 OFF
Input Shift
4 OFF
Temperature Sensor
Standard
5 ON
Scale Indication
6 ON
PID Constant Indication