Switch settings ld-64, Turning time/data rate/ connected units, Selection of 2- or 4-wire – Westermo LD-64 User Manual
Page 17: Selection of master/slave, Selection of bits

17
6073-2002
Turning Time/Data rate/
Connected units
S1
ON
1 2 3 4 5 6 7 8 9
S1
ON
1 2 3 4 5 6 7 8 9
S1
ON
1 2 3 4 5 6 7 8 9
S1
ON
1 2 3 4 5 6 7 8 9
S1
ON
1 2 3 4 5 6 7 8 9
S1
ON
1 2 3 4 5 6 7 8 9
S1
ON
1 2 3 4 5 6 7 8 9
S1
ON
1 2 3 4 5 6 7 8 9
S1
ON
1 2 3 4 5 6 7 8 9
S1
ON
1 2 3 4 5 6 7 8 9
20
Number**
of units
20
20
20
20
20
20
15
10
5
Selection of 2- or 4-wire
4-wire
S1
ON
1 2 3 4 5 6 7 8 9
2-wire
S1
ON
1 2 3 4 5 6 7 8 9
Selection of Master/Slave
Slave
S1
ON
1 2 3 4 5 6 7 8 9
Master
S1
ON
1 2 3 4 5 6 7 8 9
Selection of bits
9
S1
ON
1 2 3 4 5 6 7 8 9
10
S1
ON
1 2 3 4 5 6 7 8 9
11
S1
ON
1 2 3 4 5 6 7 8 9
*
S1
ON
1 2 3 4 5 6 7 8 9
Selection of 2-wire RS-485 or 4-wire RS-422.
For RS-232 S1:1 can be ignored.
Switch settings LD-64
0.4 ms
2 400 bit/s
Turning-
time
Transmission*
rate
0.2 ms
4 800 bit/s
0.1 ms
9 600 bit/s
50 µs
19 200 bit/s
25 µs
38 400 bit/s
16 µs
62 500 bit/s
11 µs
93 750 bit/s
9 µs
115.2 kbit/s
6 µs
187.5 kbit/s
3 µs
375 kbit/s
* Use this setting for synchronous or other
asynchronous protocols.
The transmitter will be active from the
startbit to 10 bit-times after the last high
databit (see example below). The speed
shall be set to
≅
10 times the required
communication speed.
Please note that only one master can be
used per system.
Start bit
1 bit = 52µs
1 bit: 1/19 200 = 52µs
Data rate 19 200
Transmitter active
Set the speed to 187.5 kbit/s
10x52µs = 520µs
↵
Example 19 200 bit/s
*) For other speeds please contact
Westermo
**) For additional units please contact
Westermo
S1:3 not used