6073-2002

LEDs for indication on LD-64

• PWR: Indicates that the converter has power.

• TD: Indicates that the converter is receiving data on RS-232/V.24, RS-485 side.

• RD:

Indicates that the converter is sending data on RS-232/V.24, RS-485 side.

• Rx1: Indicates received data on fiber channel 1.

• Rx2: Indicates received data on fiber channel 2.

• Tx1: Indicates that the converter is sending data on fiber channel 1 from RS-232/V.24, RS-485 side.

• Tx2: Indicates that the converter is sending data on fiber channel 2 from RS-232/V.24, RS-485 side.

Specifications LD-64

Transmission

Asynchronous

*

, half duplex or simplex

Interface 1

EIA RS-232/ITU-T V.24
9-position screw block
EIA RS-422/RS-485/ITU-T V.11
5-position screw block

Interface 2

4 ST-connectors, see table of power budget

Data rate

2 400 bit/s – 115.2 kbit/s (RS-232-C) 2 400 bit/s – 375 kbit/s
(RS-422/485)

Indicators

Power, TD, RD, TX1, TX2, RX1, RX2

Temperature range

5–50°C, ambient temperature

Humidity

0–95% RH without condensation

Dimension

55x100x128 mm (WxHxD)

Weight

0.6 kg AC / 0.3 kg DC

Mounting

On 35 mm DIN-rail

Power supply alternatives

Model description

LD-64

LD-64

LD-64

LD-64

LD-64

AC

115V AC

DC

36–55V DC

HV

Power supply

230V AC

115V AC

24V DC

48V DC

95–240V AC±10%

+15/–10%

+15/–10%

+50/–50%

+15/–25%

110–240V DC±10%

Frequency

48–62Hz

48–62Hz

48–62Hz / –

Fuse, F2

100mA S

100mA S

1.6A S

1.6A S

1A T Wickmann

5x20 mm

5x20 mm

5x20 mm

5x20 mm

Littelfuse

Littelfuse

Littelfuse

Littelfuse

Power consumption

20mA

40mA

3W

3W

40mA

Isolation, RMS

Power supply

3 000V

3 000V

1 500V

1 500V

3 750V

* Synchronous protocols can be transmitted under certain circumstances.