Sat 3p installation guide, Energy consumption screen – WattMaster WCC III part 19 User Manual
Page 12
WCC III Technical Guide
18-10
18. SAT 3P INSTALLATION GUIDE
The WCC III system has 50 Energy Consumption Screens.
The number directly under the ENERGY CONSUMPTION
SUMMARY title is the number of the screen. To change the
number, move the cursor to this fi eld, enter the number you would
like, and then press
.
Satellite #: 1
Enter the number of the satellite controller which has the pulse
type kw meter connected to it.
NOTE:
The pulse meter must be connected to the analog
input #1 on the satellite controller, and the pulse switch on the
front of the satellite controller must be in the “On” position and
a 5 VDC signal (from the Satellite’s V-Out) must be connected
to one side of the pulse meter contact.
Figure 18-6: Energy Consumption Screen
E N E R G Y C O N S U M P T I O N S U M M A R Y
1
08:29
1/30
Kansas City (On the Wall) System
------------------ Current Consumption Statistics ---------------
Satellite #: 24
Current Demand: 1,200 KW
Consumption since last reset: 13 KWH
Reset
by:
NewDay
being
ON
Description: Energy Consumption
Demand from: GA O
-------------Energy Consumption History-------------
Today
Yesterday
This Month
Last Month
Consumption:
13 KWH
28 KWH
456 KWH
-1,970 KWH
Peak Demand: 1,200 KW
1,201 KW
1,201 KW
1,800 KW
Time of Peak:
10:20
00:01
00:01 01/01
00:01 12/01
Consumption Past 60 Days in KWH:
Average over 0 0 in KWH:
HOME for menu
Energy Consumption Screen
Current Demand and Consumption Since Last Reset:
The current demand and the current consumption since last reset
are automatically displayed here. To reset the consumption, select
from the Top Menu Bar and then select
.
The following units may be selected for consumption by placing
the cursor over the units for the “Consumption since last reset,”
pressing the
until the desired units appear, and then
pressing
.
KWH = 1 KWH
DKH = 10 KWH
HKH = 100 KWH
MWH = 1,000 KWH
DMH = 10,000 KWH
HMH = 100,000 KWH
GWH = 1,000,000 KWH
DGW = 10,000,000 KWH
5428 KWH will appear as 543 DKH
5428 KWH will appear as 54 HKH, etc.