beautypg.com

4 automatic control wiring, 5 automatic control wiring - 24 volt relay module, 6 automatic control wiring - 110 volt logic pump – Watson-Marlow Qdos30 Universal User Manual

Page 4: 1 optional input lead, 2 wiring up the terminal connectors, 3 24 volt relay module pcb connectors

background image

EN

4

Watson-Marlow qdos30 pumps product safety information

4 Automatic control wiring

Interfacing the pump with other devices is by means of two IP66 rated five pole M12 connectors mounted

on the front of the pump. M12 connectors with flying lead cables can be purchased as an accessory from

Watson-Marlow. The function of each of the leads is labelled.

Output

connection

Input

connection

It is the user’s responsibility to ensure the safe and reliable operation of the pump under remote and

automatic control.

Never apply mains power to the five pole M12 connectors. Apply the correct signals to

the pins, as shown below. Limit signals to the maximum values shown. Do not apply

voltage across other terminals. Permanent damage may result.

All input and output terminals are separated from mains circuits by reinforced

insulation. These terminals must only be connected to external circuits that are also

separated from mains voltages by reinforced insulation as a minimum requirement.

4.1

Optional input lead

Inverting the response is set up in software. Do not invert the polarity of the terminals.

If the polarity is inverted the motor will not run.

5 Automatic control wiring - 24 volt relay module

5.1

24 volt relay module: cover removal and refitting

Ensure that the 24 volt logic module cover is correctly secured at all times by all four

screws. Failure to do so may compromise the IP66 (NEMA 4X) protection.

5.2

Wiring up the terminal connectors

Ensure that unused openings on the module are sealed using the blanking plugs

provided. Failure to do so will result in loss of ingress protection.

5.3

24 volt relay module pcb connectors

Never apply mains power to the terminals within a qdos30 24V relay module. Apply

the correct signals to the terminals shown below. Limit signals to the maximum

values shown. Do not apply voltage across other terminals. Permanent damage, not

covered by warranty, may result. The maximum load on the relay contacts of this

pump is 24VDC at 1.0A. Note that the maximum switching capacity on DC is 30W.

6 Automatic control wiring - 110 volt logic pump

6.1

110 volt logic module: cover removal and refitting

Ensure that the 110 volt logic module cover is correctly secured at all times by all four

screws. Failure to do so may compromise the IP66 (NEMA 4X) protection.