beautypg.com

Heetsheet, Vessel heating/cooling system, Inspection of system – Thermon HeetSheet User Manual

Page 4

background image

Form T

S

P0026U-1

101 © T

hermon Manufacturing Co. Printed in U.S.A.

Illustration G: Typical HeetSheet Installation

8. Install ThermoTube

®

steam supply and return tubing to

collection manifolds and properly terminate all inlet and
outlet media connections using an FAK-7 end seal kit. The
steam supply should start at the highest point of the
HeetSheet so that flow is generally downward to avoid
trapping water during shutdown periods (see Illustration
G). Each panel should utilize a steam trap to prevent pref-
erential steam flow.

9. In situations where excessive moisture is expected or ther-

mal insulation will not be installed immediately following
HeetSheet installation, flashing should be installed using
waterproof mastic to prevent water from accumulating
behind the panel.

Inspection of System . . .

1. Thoroughly inspect banding after installation is complete

to verify proper tension.

2. After all connections to the supply header and collection

manifolds have been completed, test the circuit for leaks
by subjecting it to steam pressure equal to or greater than
that which is to be used in the system or preferably with
suitable hydrostatic tests. Repair any leaks and retest the
system.

HeetSheet

®

Vessel Heating/Cooling System

To Trap and
Condensate
Return Manifold

FAK-7

HeetSheet

40 x 6mm
Steel Strap

ThermoTube

Flashing
(if required)

Waterproof Mastic

Welded Stud
Attachment Method

From Steam

Supply Manifold

THERMON . . . The Heat Tracing Specialists

®

www.thermon.com

Corporate Headquarters
100 Thermon Dr.

PO Box 609

San Marcos, TX 78667-0609

U.S.A.

Phone: +1 512-396-5801

Facsimile: +1 512-396-3627

European Headquarters
Boezemweg 25

2641 KG Pijnacker

PO Box 205

2640 AE Pijnacker

The Netherlands

Phone: +31 (0) 15-36 15 370

Facsimile: +31 (0) 15-36 15 379