Step 8

Mount the CKTES/PETK on a flat surface, with expansion loop of 150 mm in the cables. Heating Cable/Cold Leads

and joint secured in place using fibre fixing tape. Application of tape shall allow a small degree of movement at the

joint and cables to cater for potential expansion and contraction of the pipeline. Do not over-tighten.

Step 9

Do not move the assembled CKTES/PETK for minimum 24 hours for complete curing.

Installation Instructions

6

150 mm

150 mm

Form TEP0107U-0512 © Thermon Manufacturing Co. Information subject to change.