Step 1
First determine the correct circuit length, then slide the screw cap and the
rubber grommet over the heating cable and cold lead cable (in case of a power
connection). Slide the housing over (one of) the heating cable(s).
Step 2
Remove 60 mm* outer jacket from both cables (*for TESH 600 up to TESH 8000, 75 mm). Separate braid strands at
the end of the outer jacket of the heating cable(s) and cold lead cable (PETK-10/11). Push back the braid away from
the heating cable to form a pigtail. Remove glass ceramic/polyamide tape. Pull the insulated conductor through the
opening in the braid of both cables.
Step 3
Twist the braid into a pig tail and trim the ends. Cut the braid of the Heating Cable at approximately 30 mm and 50 mm
for the Cold Lead / 2
nd
Heating cable. Cut the conductors at 50 mm* and 30 mm* (*for TESH 600 up to 8000, cut 65
and 45 mm).
Step 4
Remove primary insulation of the heating conductor and cold lead over a length of 15 mm (*in case of Cold lead or
TESH 2,9 and TESH 4,4 remove 20 mm, for TESH 600 up to 8000 remove 30 mm). **Side view of spacer in image.
Installation Instructions
4
Form TEP0107U-0512 © Thermon Manufacturing Co. Information subject to change.
Items drawings
Item
Description
A
Heating Cable
B
Cold Lead/Heating Cable
C
Screw Cap
D
Spacer
E
Sealant
F
Crimp Connector
G
Grommet
H
Housing
I
Braiding
J
Conductor
K
Outerjacket
L
Primary Insulation