beautypg.com

Thermon PETK-10 User Manual

Page 5

background image

Step 1

First determine the correct circuit length, then slide the screw cap and the
rubber grommet over the heating cable and cold lead cable (in case of a power
connection). Slide the housing over (one of) the heating cable(s).

Step 2

Remove 60 mm* outer jacket from both cables (*for TESH 600 up to TESH 8000, 75 mm). Separate braid strands at
the end of the outer jacket of the heating cable(s) and cold lead cable (PETK-10/11). Push back the braid away from
the heating cable to form a pigtail. Remove glass ceramic/polyamide tape. Pull the insulated conductor through the
opening in the braid of both cables.

Step 3

Twist the braid into a pig tail and trim the ends. Cut the braid of the Heating Cable at approximately 30 mm and 50 mm
for the Cold Lead / 2

nd

Heating cable. Cut the conductors at 50 mm* and 30 mm* (*for TESH 600 up to 8000, cut 65

and 45 mm).

Step 4

Remove primary insulation of the heating conductor and cold lead over a length of 15 mm (*in case of Cold lead or
TESH 2,9 and TESH 4,4 remove 20 mm, for TESH 600 up to 8000 remove 30 mm). **Side view of spacer in image.

Installation Instructions

4

Form TEP0107U-0512 © Thermon Manufacturing Co. Information subject to change.

Items drawings

Item

Description

A

Heating Cable

B

Cold Lead/Heating Cable

C

Screw Cap

D

Spacer

E

Sealant

F

Crimp Connector

G

Grommet

H

Housing

I

Braiding

J

Conductor

K

Outerjacket

L

Primary Insulation