Tecfluid CP420P User Manual
Page 10
10
7
KEYBOARD INHIBITION AND “WRITE PROTECT”
The transmitter has a jumper situated behind the PCB at the top left corner, which can be
used to avoid changes in the configuration. When the jumper is removed, the keyboard is
disabled and the HART
TM
write protect is activated, thus inhibiting any changes in the
configuration.
To gain access, remove the frame from the housing and remove the front plate forward.
8 TECHNICAL
CHARACTERISTICS
8.1 Power
supply
2 wires, by means of the current loop.
The instrument has a protection diode to avoid damage if the power supply is connected
with inverted polarity .
Nominal voltage:
8 ... 36 VDC
Power consumption:
≤ 20 mA
8.2 Totalizer
N. of digits:
7
Size of the digit:
8 mm
Reset:
By means of keyboard
8.3
Flow rate Indication
N. of digits:
5
Size of the digit:
5 mm
8.4 Housing
Ingress protection (once installed in a panel):
Back
IP30
Front
IP50
Silicone sleeves for the front side, for an IP65 ingress protection, are available.
Ambient temperature range:
0 … +60 ºC
8.5 Input
terminals
The pulse input is connected to a screw terminal block marked as Pulse. Numeration is as
following.
Terminal n.
Series COVOL
Series TM
1
Common
Live
2
Live
Live
8.6 General
This material conforms with the following directives:
2004/108/EC
Electromagnetic
Compatibility.
2002/96/EC Waste
electrical and electronic equipment.