Resume of the principal communication characteristics:
Manufacturer, Model and Revision
Tecfluid S.A., TH5H, Rev. 0
Device type
Transmitter
HART revision
6.0
Device Description available
No
Number and type of sensors
1
Number and type of actuators
0
Number and type of host side signals
1, 4 – 20 mA analogic
Number of Device Variables
2
Number of Dynamic Variables
1
Mappable Dynamic Variables
No
Number of Common Practice Commands
12
Number of Device Specific Commands
2
Bits of Additional Device Status
12
Alternative working modes?
No
Burst mode?
No
Write Protection?
Yes
Electrical characteristics referred to the analog loop and communications:
Reception
impedance
Rx
>
3,3
MΩ
Cx
<
1000
pF
6 “WRITE
PROTECT”.
The instrument has a jumper that can be used to avoid changes in the configuration.
When the jumper is connected the instrument can be configured via HART
TM
. When the
jumper is removed, “Write Protect” is activated for HART
TM
, thus avoiding any changes in
the configuration.
7 MAINTENANCE
No special maintenance is required.