r1 =
Input Type and Range Value
0 =
TC
J
From
-100
to
1000
°C
1 =
TC
K
From
-100
to
1370
°C
2 =
TC
T
From
-200
to
400
°C
3 =
TC
E
From
-100
to
800
°C
4 =
TC
N
From
-100
to
1400
°C
5 =
TC
S
From
-50
to
1760
°C
6 =
TC
R
From
-50
to
1760
°C
7 =
TC
B
From
0
to
1820
°C
8 =
TC
L
From
-100
to
900
°C
9 =
TC
U
From
-200
to
600
°C
10 =
TC
G
From
0
to
2300
°C
11 =
TC
D
From
0
to
2300
°C
12 =
TC
C
From
0
to
2300
°C
13 =
TC Plat. II
From
-100
to
1400
°C
14 =
RTD Pt 100 From
-200
to
850
°C
15 =
Linear
From
0
to
60
mV
16 =
Linear
From
12
to
60
mV
17 =
Linear
From
0
to
20
mA
18 =
Linear
From
4
to
20
mA
19 =
Linear
From
0
to
5
V
20 =
Linear
From
1
to
5
V
21 =
Linear
From
0
to
10
V
22 =
Linear
From
2
to
10
V
23 =
TC
J
From
-150
to
1830
°F
24 =
TC
K
From
-150
to
2500
°F
25 =
TC
T
From
-330
to
750
°F
26 =
TC
E
From
-150
to
1470
°F
27 =
TC
N
From
-150
to
2550
°F
28 =
TC
S
From
-60
to
3200
°F
29 =
TC
R
From
-60
to
3200
°F
30 =
TC
B
From
32
to
3300
°F
31 =
TC
L
From
-150
to
1650
°F
32 =
TC
U
From
-330
to
1110
°F
33 =
TC
G
From
0
to
4170
°F
34 =
TC
D
From
0
to
4170
°F
35 =
TC
C
From
0
to
4170
°F
36 =
TC Plat. II
From
-150
to
2550
°F
37 =
RTD Pt100
From
-330
to
1560
°F
r2 = Decimal Point Position
(Available only for linear range r1 = 15 to 22)
_ _ _ _ .
= No decimal
_ _ _ . _
= One decimal place
_ _ . _ _
= Two decimal places
_ . _ _ _
= Three decimal places
r3 = Low Scale Range Value
(Available only for linear range r1 = 15 to 22)
Range: From -1999 to 9999
r4 = High Scale Range Value
(Available only for linear range r1 = 15 to 22)
Range: From -1999 to 9999
r5 = Offset Adjustment
Range: From -500 to 500
Offset value algebraically added to the measured value.
r6 = Time Constant for Filter on Displayed Value
Range: From 0 (filter OFF) to 8 seconds.
(First order filter with selected time constant.)
r7 = Alarm Action on Fault
uP = The alarm assumes an upscale reading.
doun = The alarm assumes a downscale reading.
C1 = Type of Limit Action
Hi. = High limit (for heating process)
Lo. = Low limit (for cooling process)
Hi.Lo = Band limit (for special process)
C2 = Acknowledgment Mode
O = The acknowledgment action is ignored if performed
when setpoint is exceeded.
I =
The acknowledgment action is recognized also
when the setpoint is exceeded. (In this case, the
control output is instantaneously restored when
process variable is within setpoint).