Figure 2 dip switch settings – Sun Pumps PCC-BT-M2 User Manual
Page 8
Figure 2 Dip Switch Settings
Switch
Switch
Description
Function
Default
Setting
Number
Position
1
OFF
Remote Switch Logic 1
Turns pump off when “RS1” and
“GND” terminals connect.
OFF
1
ON
Remote Switch Logic 1
Turns Pump on when “RS1” and
“GND” terminals connect.
OFF
2
OFF
Remote Switch Logic 2
Turns pump off when “RS2” and
“GND” terminals connect.
OFF
2
ON
Remote Switch Logic 2
Turns pump on when “RS2” and
“GND” terminals connect.
OFF
3
ON
5 Amp Setting
Sets current regulation to 5
amps.
OFF
4
ON
7.5 Amp Setting
Sets current regulation to 7.5
amps.
OFF
5
ON
10 Amp Setting
Sets current regulation to 10
amps.
OFF
6
ON
14 Amp Setting
Sets current regulation to 14
amps.
OFF
7 & 8
OFF
RS1 Switch Turn-On Timer
No Timer is Active
OFF
7 Only
ON
RS1 Switch Turn-On Timer
3 Minute Turn-On Timer
OFF
8 Only
ON
RS1 Switch Turn-On Timer
7 Minute Turn-On Timer
OFF
7 & 8
ON
RS1 Switch Turn-On Timer
10 Minute Turn-On Timer
OFF
9
ON
Display Freeze
Holds display on current screen
OFF
10
ON
MPPT Disable
Disables the MPPT function of
the controller. For testing only.
OFF