Fire sprinkler heads must be located at an appropriate distance from the heater. This distance

may exceed the published clearance to combustibles. Certain applications will require the use of high temperature
sprinkler heads or relocation of the heaters.

Sprinkler systems containing propylene glycol or other flammable substances are not to be used in conjunction
with this heater without careful consideration for and avoidance of potential fire or explosion hazards. For further
information consult NFPA 13. Always observe applicable state and local codes.

5)

DK SERIES SPECIFICATIONS

MODEL NO.

BTU/HR INPUT

NUMBER

OF BURNERS

ORIFICE SIZE

SHIPPING WEIGHT

MINIMUM

MOUNTING

HEIGHT (feet)

Natural Gas

Propane Gas

DK30-N5C

33,000

1

3/32”

n/a

30 lbs.

11

DK35-N5C

35,000

1

#41

n/a

30 lbs.

12

DK40-N5C

40,000

1

#38

n/a

30 lbs.

12

DK60-N5C

65,000

2

3/32”

n/a

35 lbs.

13

DK70-N5C

70,000

2

#41

n/a

35 lbs.

13

DK80-N5C

80,000

2

#38

n/a

35 lbs.

14

DK100-N5C

100,000

3

#41

n/a

48 lbs.

15

DK120-N5C

120,000

3

#38

n/a

48 lbs.

16

DK140-N5C

140,000

4

#41

n/a

58 lbs.

17

DK160-N5C

160,000

4

#38

n/a

58 lbs.

18

DK33-L5C

33,000

1

n/a

#52

30 lbs.

11

DK66-L5C

66,000

2

n/a

#52

35 lbs.

13

DK100-L5C

99,000

3

n/a

#52

48 lbs.

15

DK132-L5C

132,000

4

n/a

#52

58 lbs.

17


MODEL SUFFIX

GAS-PIPE

CONNECTION:

 One Orifice Per Burner

Gas Type:

Ignition System:

N = Natural
L = Propane

5 = Direct Spark (115 Volt / 0.40 Amp / 60 Hz)

1/2” NPT (Female)


*MOUNT HEATERS AS HIGH AS POSSIBLE. Minimums are shown as a guideline for human comfort and uniform
energy distribution for complete building heating applications. Consult your Space-Ray representative for the
particulars of your installation requirements.








6

INSTALLER

In locations used for storage of combustible materials where they may be stacked below the heater,
NFPA 54 requires that the installer must post signs that will “specify the maximum permissible
stacking height to maintain the required clearances from the heater to combustibles.” Space-Ray
recommends posting these signs adjacent to the heater thermostat or other suitable location that will
provide enhanced visibility. It is important to provide warnings to alert individuals of potential hazards
and safety actions. Posted signs should state the hazards for the particular application and be legible
to building occupants.